12 MAG816 - Installation and Operation Manual
First
4 Zone
Expander
Second
4 Zone
Expander
First
4 Sounder
Expander
Control
panel
1234 5678
1234
3.7 4-Sounder Expander
• 1 - Mounting holes.
• 2 - Connector for connecting of additional
4-sounder expander.
• 3 - LED indication for troubles in the sounder
circuits. In case of a trouble in any of the sounder
circuit SND1 - 4 the LED of the respective
sounder circuit will light on together with
GENERAL FAULT and SOUNDER FAULT/
DISABLE indicators on the front panel.
• 4 - Connector for connecting:
а) To a 4-zone expander.
b) To a previous 4-sounder expander.
c) To the control module.*
• 5 - Mounting holes for placing a lightpipe for the
front panel LED indication, Position 15, page 31.*
• 6 - LEDs Sounder status indication.*
* Note: Just in case, when the panel is in
Repeater Mode (a jumper is set on the SLAVE
position).
Performance and Connecting of the 4-Sounder Expander
There is a correspondence between the zone numbers and the sounders - ZONE 1 of
the 4-zone expander corresponds to SOUNDER 1 of the 4-sounder expander, ZONE
2 to SOUNDER 2, and so on. In case of re in ZONE 1, SOUNDER 1 will operate
continuously and Sounders 2 ÷ 4 of the expander will be pulse activated - 2 sec. sound/
2 sec. silent.
The method of adding of 4-sounder expander is analogical to that of adding a 4-zone
expander module, see Figure 14. Note: At Step 3 mount the resistors R-10K from the
supplied spare parts kit (position 16, page 31) to the sounder expander terminals.
ATTENTION: Do not connect or disconnect the expander when the power
is on! Before connecting or disconnecting the expander you SHOULD
check whether the main and the stand-by power supplies are OFF!
Note: Only a module of the same type can be added to the 4-sounder
expander. For the proper performance of the re alarm panel observe
the connection sequence presented in Figure 16a. In case of improper
connection (Figure 16b), an error signal will be generated when the
power supply is switched on - the LEDs of the zones connected after the
4-sounder expander will begin to blink and the GENERAL FAULT LED
remains permanently lit.
а)
Figure 16.
!
First
4 Zone
Expander
First
4 Sounder
Expander
Second
4 Zones
Expander
Control
panel
1234
1234
5678
b)
Figure 15.
!