22 MAG816 - Installation and Operation Manual
6.3 Buttons
Button Description
Activating sounders.
Deactivating sounders.
Deactivating the internal buzzer.
Initializing of the start-up procedure.
Conrming the introduced changes.
Enabling / Disabling of zones / sounders.
Test Mode; scroll forward zones.
6.4 LED Indication
LED Description
FIRE
(two red)
Fire in the premises.
GENERAL FAULT
(yellow)
Main Fault indicator.
SOUNDER FAULT/DISABLE
(yellow)
Lights permanently at disabled sounders.
Blinks at trouble in the sounder circuit.
OUTPUT DELAY
(yellow)
Lights permanently at programmed outputs time de-
lay (a jumper is set on the TIME DELAY terminal).
ENABLE/DISABLE
(yellow)
Lights permanently at disabled zones/sounders.
Blinks during enabling/disabling of zones or sound-
ers.
TEST
(yellow)
Blinks during “One Man” Test of a zone.
POWER SUPPLY 230V
(green)
Blinks permanently in normal operating mode, indi-
cates presence of main power supply 230V.
LED 1- 16
(yellow-red)
Zone indication.
Lights up in red at Fire in the zone.
Lights up in yellow at disabled zone.
Blinks in yellow:
- 1 blink per second at trouble in the zone;
- 2 blinks per second at “One Man” Test and
disabling of zones.