MAG816 - Installation and Operation Manual 25
“One Man” Test
The “One Man” Test mode gives the installer the possibility to test the efciency of the
system - whether the detectors react to smoke, heat, etc.
To “One Man” Test a zone:
• Press
button: TEST LED will start blinking.
The ZONE 1 LED blinks in yellow
(2 blinks per second).
ZONE 1 is in test mode.
Test a detector from this zone whether it
react to smoke, heat, etc.
MAG816 will activate the sounders
for about 2 seconds to conrm the
provoked re alarm.
• Press
button to continue
with the system testing: TEST LED will continue blinking.
The ZONE 1 LED lights out (the zone is
not longer in test mode).
The ZONE 2 LED blinks in yellow
(2 blinks per second).
ZONE 2 is in test mode.
Test a detector from this zone whether it
react to smoke, heat, etc.
MAG816 will activate the sounders
for about 2 seconds to conrm the
provoked re alarm.
Continue the system testing by pressing the
button. The exit from the “One
Man” Test mode is automatic after the end of the test procedure in the last zone, or at
any time by pressing
button.
A sound signalization is activated at every Service Mode entering .
The signalization is deactivated by pressing
button.
!