28 MAG816 - Installation and Operation Manual
GENERAL CONNECTION CIRCUIT OF MAG816
Expander
Zones / 4 Sounders4
CALL
POINTS
ZONE
Expander
Zones / 4 Sounders4
Expander
Zones / 4 Sounders4
Expander
Zones / 4 Sounders4
SND 1
324V / 0, A
SND 2
324V / 0, A
SND 3
324V / 0, A
SND 4
324V / 0, A
FAULT
RELAY
FIRE
RELAY
Rx
Tx
NO
NC
NC
NO
COM
COM
CC
GND
+AUX
MAG8plus MAIN BOARD
MASTER
SLAVE
DOUBLE
1
2
3
4
POWER
EXP
uPFault
SND1
SND2
SND3
SND4
FAULTS
EARTH
AUX
RPT
AC
BATT LOW/LOST
Jumper to Enable/Disable
Earth FaultIndication
AC 230V/50-60 Hz
FUSE:
(T) 230V
A2
LN
NL
ZONE NUMBERS: 1, 2, 3, 4, 5 ... 16
SOUNDER NUMBERS: 1, 2, 3 ... (16 - ZONENUMBERS)
Connection Diagram
Expander4Zones
Connection Diagram
Expander4Sounders
R=10K
Thresholds for
zone conditions:
10
10
I<2mA
I=2- mA
I= -110 mA
I>110 mA
Open circuit
fault condition
Normal condition
Fire alarm condition
Short circuit condition
EOL
RED
BLACK
DETECTOR DETECTOR
CALL
POINT
CALL
POINT
LAST DEVICE
ON ZONE
RECOMMENDED USE SCHOTTKY
DIODE TYPE BYV-1060
ZONE
FIRE ALARM
CONTROL PANEL
TIME
(min )
DELAY
in utes
Up to 32 conventional
detectors, with
consumption<200 Aat
normal state and unlimited
number of manual
call points.
µ
BROWN
BLACK
RED
Expander
4 Sounders
SND 1
1524V /0,A
SND 2
1524V /0,A
SND 3
1524V /0,A
SND 4
1524V /0,A
SND1
SND2
SND3
SND4
ZONE1
ZONE2
ZONE3
ZONE4
DD
EOL
DD
EOL
DD
EOL
DD
EOL
D
Expander
4 Zones
EN54-2: 1997+AC:1999+A1:2006
EN54-4: 1997+AC:1999+A1:2002+A2:2006
MAG816